Emergency light discharge testing in Melbourne

Emergency light discharge testing for Melbourne apartment blocks, offices and warehouses: what the test checks, what gets recorded and what it costs.

Emergency light testing checks that every emergency luminaire and exit sign in a building switches to battery when mains power fails and stays lit for the whole test period. In Victoria the building owner has to keep emergency lighting working as an essential safety measure, and the results go into the maintenance records behind the annual report. The testing itself is quoted and carried out by independent providers; this site passes your enquiry to them.

Illustrative photo for Emergency light discharge testing in Melbourne

Which buildings need emergency lighting tested?

The Building and Plumbing Commission says essential safety measures apply to every building apart from a house or outbuilding. That takes in apartment blocks (Class 2), backpacker accommodation and the residential parts of hotels (Class 3), offices (Class 5), shops and cafes (Class 6), car parks and storage buildings (Class 7), factories (Class 8) and public buildings such as clinics and schools (Class 9). Emergency lighting, exit signs and emergency power supply all appear in Schedule 8 of the Building Regulations 2018.

What must be tested, and how often, depends on when the building went up:

Building Where the maintenance requirement comes from
Built or altered since 1 July 1994 The list of essential safety measures, with performance level and maintenance frequency, issued with the occupancy permit or certificate of final inspection
Built before 1 July 1994 A general duty to keep safety equipment maintained and fulfilling its purpose; an owner can ask a building surveyor to prepare a maintenance schedule
Any building after new works Ask the municipal or a private building surveyor, because alterations can change the measures required

Find your occupancy permit or maintenance determination before you ask for prices. Any provider worth hiring will ask to see it.

What happens during a discharge test

The technician isolates normal supply to the emergency lighting circuits, usually one floor or one circuit at a time, so each fitting falls back to its own battery or to the central battery. They walk the area to confirm every fitting came on, then return at the end of the test period to find any that faded or went dark early. Every fitting that fails goes on the defect list.

AS/NZS 2293.2, the Australian and New Zealand standard for routine service of emergency lighting and exit signs, sorts faults into three grades:

  • a critical defect, which makes the system inoperative, for example a failed central battery
  • a non-critical defect, for example one dead luminaire in a room lit by several
  • a non-conformance, for example missing records, illegible labels or no location plan

The standard also calls for a survey from floor level to pick up changes that affect the system, such as a new partition, taller shelving or a fit-out that hides an exit sign. The preview on the Standards Australia page for AS/NZS 2293.2 sets out those definitions.

Signs a building is overdue

  • The red ESM box or log book has no entry for the last service round.
  • Exit signs are dim, flickering or have yellowed diffusers.
  • The test button on a fitting does nothing, or a test panel is showing faults.
  • A tenant has moved walls or added racking since the last visit.
  • The building changed hands and nobody can find the maintenance schedule.

Testing approaches compared

Approach Suits What to watch
Manual discharge test by a technician Small and mid-size buildings with self-contained fittings Normal lighting on the tested circuits is off for the test period, so plan around trading hours and night shifts
Self-test fittings with a local indicator Sites that want fewer access visits Someone still reads and records each indicator; a fitting whose test system has stopped working is itself a defect
Monitored or addressable system Towers, campuses, large warehouses Higher install cost; reports still need checking by a competent person and copying into the log book
Central battery system Some older and larger buildings The battery bank has its own maintenance standards, and one failure can black out a whole floor

What a provider needs from you

  • The address and the number of floors, car park levels and tenancies
  • An approximate count of emergency lights and exit signs, or the last service report
  • A copy of the occupancy permit, maintenance determination or schedule
  • Access details: keys, swipe cards, plant rooms and tenancies that need notice
  • Whether some circuits can lose normal lighting while the test runs

What it costs

A published Melbourne cost guide puts testing at $8 to $22 per fitting, or a flat $110 to $250 per visit on a small site. Fittings that fail are repaired or replaced on top of that, usually at a commercial electrician’s hourly rate. The emergency lighting cost guide explains what pushes a quote up or down.

Rules and who can do which part

Owners must maintain essential safety measures so they operate satisfactorily, and must keep records of every maintenance check and repair. The CFA says exit signs and emergency lighting must be installed by an electrician. Testing is routine service, but swapping a fitting is electrical installation work: in Victoria the electrician has to work for a Registered Electrical Contractor, and a Certificate of Electrical Safety records the job.

A careful provider will not mark a fitting as passed without running it on battery, will not leave a building with emergency circuits isolated overnight, and will not backfill log book entries for rounds that never happened.

Melbourne buildings

Inner Melbourne has a lot of older buildings converted to apartments and offices, from loft conversions in the Melbourne CBD to the warehouse conversions of Collingwood. Those often have fittings added in stages over several fit-outs and no single schedule. Newer towers can run to hundreds of fittings across lobbies, stairs and car park levels, with an occupancy permit that sets the frequency.

What to do next

If the test finds fittings that fail, the usual fixes are emergency light battery replacement or a move to LED emergency fittings. To have testing priced, send the building details through the quote form with your fitting count and access notes.

Send a job enquiry

Frequently asked questions

Will the lights go off in my building during a discharge test?

Normal lighting on the circuits being tested is switched off while the fittings run on battery. Providers usually work one floor or zone at a time, and you can ask for testing outside trading or shift hours.

How long does a discharge test take?

It depends on the test period the fittings must achieve and the size of the building. A large building is normally tested in stages over one or more visits so that no area is without normal lighting for long.

What happens to fittings that fail?

They are recorded as defects in the service report and log book, graded by how serious they are. Repairs, usually a new battery or a new fitting, are quoted separately unless your agreement includes them.

Can self-test emergency lights replace manual testing?

They can reduce the time spent on site, but the results still have to be read, checked and recorded by a competent person. A self-test fitting whose test function has failed is itself a defect.

Does the tester need to be an electrician?

The testing is routine service, but replacing or rewiring a fitting is electrical work that needs a licensed electrician working for a Registered Electrical Contractor. Many testing businesses are electrical contractors for that reason.