Exit sign testing and replacement
Exit sign testing and replacement for Melbourne strata, retail and industrial buildings: failure signs, visibility problems, replacement options and rules.
An exit sign has to stay lit and readable when the power goes out, so testing means running each sign on its battery, checking it can be seen from the path people will use, and replacing any that fail. Signs are part of the emergency lighting system that Victorian building owners must maintain. Providers in our referral network quote and do the work; you deal with them directly.

How exit signs fail
The CFA describes exit signs as bright green, illuminated signs above doorframes that must stay visible in a power failure. In practice they fail in a handful of ways:
- Battery fade. The sign is lit on mains but drops out early on battery. Only a discharge test shows this.
- Light source failure. Older fluorescent signs lose tubes; LED signs dim slowly as the light source ages.
- Damaged diffuser or legend. Cracked, yellowed or painted-over faces make the running figure hard to read.
- Hidden sign. Shelving, pallet racking, flyers, decorations, partitions or a new bulkhead block the line of sight.
- Wrong sign after a fit-out. A door was moved or closed off, but the sign above it still points people that way.
The last two are the ones owners miss, because the sign itself passes its test. The CFA suggests adding signs or emergency lights where a permanent structure blocks one.
What an exit sign check covers
A technician working to AS/NZS 2293.2 will usually:
- Confirm each sign shown on the location plan is still there, and note any that are not on the plan.
- Run the signs on battery for the test period and record which drop out.
- Look along each exit path from floor level to confirm the sign can be seen and points the right way.
- Check that the sign face, housing and mounting are sound.
- List each fault as a critical defect, non-critical defect or non-conformance and hand you the record.
Exit doors, and the paths of travel to them, are separate essential safety measures. Occupiers must keep them clear and usable, so a provider who finds a locked or blocked exit should report it even though it is not a lighting fault.
Repair or replace?
| Situation | Usual fix | Notes |
|---|---|---|
| Sign fails discharge test, housing sound | Replace the battery | Cheapest fix if the battery is a standard part for that model |
| Fluorescent sign failing repeatedly | Replace with an LED exit sign | Removes tube replacement; the old tubes contain mercury and need proper disposal |
| Sign hidden by racking or a new wall | Move the sign or add another | Check with a building surveyor first if it changes the approved layout |
| Sign above a door that is no longer an exit | Remove or change it on the surveyor’s advice | Never just switch it off and leave it |
| Self-test sign with a dead test circuit | Repair or replace the sign | Counts as a defect even if the sign still lights |
Rules that apply
Exit signs are listed in Schedule 8 of the Building Regulations 2018, and the owner must keep them operating satisfactorily. Design and placement come from AS/NZS 2293.1, and the signs themselves are made to AS/NZS 2293.3. Where building work moves or closes an exit, get a building surveyor to confirm what the essential safety measures should now be before signs are moved, as the Building and Plumbing Commission recommends.
Replacing or relocating a sign is electrical work. The person doing it must hold a licence from Energy Safe Victoria and work for a Registered Electrical Contractor, who then issues a non-prescribed Certificate of Electrical Safety. Energy Safe says that certificate should reach the customer within 30 days.
What a careful provider will not do
- Swap a sign for a cheaper unit that is not rated for the location or mounting
- Relocate signs during a fit-out without checking the approved design
- Leave a removed sign’s wiring live and unterminated in the ceiling
- Pass a sign that cannot be seen from the path of travel because it lit up on test
What a provider needs from you
- The number of exit signs and where they are: stairs, car park, warehouse floor, tenancies
- Whether they are fluorescent, LED, self-test or on a central system, if you know
- Recent changes: new tenants, racking, partitions or closed doors
- Ceiling heights and any lift or scaffold access needed in high-bay areas
- The last service report and location plan from the log book
Costs
A published Melbourne price table puts a sign test at $8 to $22 per fitting, the same rate as an emergency light. Replacement is quoted as parts plus labour, and the same source lists commercial electrician labour at $100 to $150 per hour. Signs that need lifts or after-hours access in a busy warehouse cost more to reach. The Melbourne cost guide shows how these rates combine on a full building.
Local buildings
Warehouses in Laverton North can have high racking between the signs and the exit doors. Converted factories and warehouses in Collingwood have often been refitted several times, and each fit-out can leave a sign that no longer matches the exits.
Next step
If several signs are fluorescent and failing, compare the cost of repeat repairs with LED emergency light upgrades. For signs that only fail on battery, battery replacement may be enough. When you are ready, request exit sign testing or replacement and list how many signs you have and where.
Frequently asked questions
- Why does an exit sign pass its test but still get flagged?
A sign can light on battery and still fail the survey if racking, a partition or a new bulkhead blocks the view, or if it points to a door that is no longer an exit.
- Can I move an exit sign myself during a fit-out?
No. Moving a sign is electrical work, and changing exit positions can alter the approved design. Use a licensed electrician and check with a building surveyor if exits are changing.
- Are LED exit signs worth it?
They remove fluorescent tubes from the maintenance list and are the usual choice when old signs keep failing. Ask how the provider will assess the LED light source at later service rounds.
- Do exit signs need to stay on all the time?
Illuminated exit signs are meant to be visible in normal conditions and in a power failure. A sign that has been switched off or disconnected should be reported and fixed, not left as it is.
- What paperwork should I get after a sign is replaced?
A service record in the log book showing the replacement and retest, and a Certificate of Electrical Safety from the Registered Electrical Contractor for the electrical work.