Log book records and the annual ESM report
Keeping emergency lighting records for the annual essential safety measures report in Victoria: what to log, who signs, how long to keep it, and costs.
Every Victorian building other than a house or outbuilding needs records of its essential safety measures maintenance, and the owner must prepare an annual essential safety measures report (AESMR) in the approved form. For emergency lighting that means a log entry for every test round, defect and repair, so the report can say the lights were maintained. Record keeping and report preparation are offered by independent providers who quote you directly; this site is a referral service.

What the law asks of owners
The Building and Plumbing Commission’s essential safety measures guide sets out the owner’s duties under Part 15 of the Building Regulations 2018:
- maintain each essential safety measure so it operates satisfactorily
- prepare an annual essential safety measures report in the approved form
- keep records of maintenance checks, safety measures and repair work
- make the records and reports available to the municipal building surveyor or the fire brigade chief officer on request after 24 hours’ notice
The owner may authorise an agent, such as a specialist maintenance contractor, to complete the annual report. The owner stays responsible for it. For Class 9 buildings, and Class 2 to 8 buildings built or altered since 1 July 1994, a current copy of the occupancy permit must be on display in the building.
The BPC’s ESM responsibilities framework adds that the records and annual reports an authority can ask for go back 10 years.
What an emergency lighting log entry should show
| Field | Why it matters |
|---|---|
| Date of the service round and the technician’s name and business | Shows who did the work and when |
| Fittings tested, by location or ID | Lets the next technician find missed or new fittings |
| Result for each fitting: pass, critical defect, non-critical defect or non-conformance | Uses the grading in AS/NZS 2293.2 |
| Repairs done and date completed | Closes out each defect |
| Defects still open and the plan to fix them | The annual report has to reflect what was not fixed |
| Changes noticed in the building | New walls, racking or tenancies that affect coverage |
AS/NZS 2293.2 treats missing records and missing baseline data as a non-conformance. A building with good fittings and no records still has a defect to fix.
Where records are kept
The CFA notes that service evidence is usually kept in a red essential safety measures box in the front entry or another common area. Copies may also be held by the owners corporation manager or the maintenance contractor. Wherever they live, the BPC’s framework says records requested by an authority must be made available within 24 hours, so the owner needs to know who holds them.
Who is responsible in strata and leased buildings
A 2022 fact sheet for apartment residents from the VBA (now the Building and Plumbing Commission) says owners corporations are responsible for maintaining a building’s ESMs, and that the owners corporation manager, on behalf of owners, makes sure they are regularly tested. In leased commercial buildings, the CFA notes that a lease may hand ESM maintenance to the tenant, so check the lease before you assume the landlord has it covered. Lot owners in a strata building must not maintain common property themselves unless the owners corporation authorises it, according to Consumer Affairs Victoria.
How the work is done
- Gather the occupancy permit, maintenance determination or schedule.
- Reconcile the fitting list with what is installed and with past service reports.
- Check each service round in the year was done and recorded at the required frequency.
- Confirm defects were repaired, or list them as open.
- Prepare the annual report for the owner or the owner’s authorised agent to sign.
Costs
A published Melbourne price table puts an annual essential safety measures report for a small commercial building at $200 to $450 per report, with that figure quoted plus GST. The same source lists warehouse, industrial and multi-storey reports as price on application. Report preparation is separate from testing; see emergency light discharge testing for test pricing and the emergency lighting cost guide for a full-year picture.
What a careful provider will not do
- Sign off a year of service rounds they did not do or cannot see records for
- Leave open defects out of the report so it looks clean
- Prepare a report without seeing the occupancy permit or maintenance schedule
- Treat the log book as the owner’s problem once the invoice is paid
Local notes
Converted older buildings in Collingwood and the CBD may date from before 1 July 1994 and have no maintenance schedule at all; the owner can ask a building surveyor to prepare one. Industrial sites in Laverton North can carry several measures, such as sprinklers, hydrants and lighting, and when each has its own contractor a single combined log book takes more effort to keep.
Next step
Ask for help with ESM records or the annual report and say how many buildings, which measures are installed and whether you have last year’s report.
Frequently asked questions
- Is the annual essential safety measures report lodged with council?
The BPC guidance describes the owner preparing it and making it available on request after 24 hours' notice to the municipal building surveyor or fire brigade chief officer. Keep it with the maintenance records.
- What if we cannot find old service records?
Start keeping complete records now, rebuild a fitting list from a site survey, and note the gap honestly. Missing records are a non-conformance to fix, not something to fill in after the fact.
- Our building is older than 1 July 1994. Do we still need records?
Yes. Owners of older buildings must keep safety equipment maintained and fulfilling its purpose. The Building and Plumbing Commission still expects records of maintenance checks and repair work.
- Where should the emergency lighting log book be kept?
The CFA describes a red essential safety measures box in the front entry or a common area, holding a logbook or individual service documents. If the manager or contractor keeps the originals, agree who produces them when the municipal building surveyor or fire authority asks.
- Who signs the annual report?
The owner, or an agent the owner has authorised, such as a specialist maintenance contractor. The duty to have it prepared stays with the owner.